Honeywell Stud Sensor C7600A User Manual

C7600A  
Solid State Humidity Sensor  
PRODUCT DATA  
FEATURES  
Long-lasting solid state sensing element is accurate  
and stable over time.  
Sensor enclosed in rugged glass-fiber reinforced  
plastic case.  
Compact size and lightweight construction for easy  
mounting in duct or on wall.  
Vents in top of cover allow air flow to internal humidity  
sensing element.  
4 to 20 mA output inversely proportional to relative air  
humidity.  
Can be used indoors or outdoors.  
GENERAL  
The C7600A Solid State Humidity Sensor senses the relative  
humidity of the return air and is used with the W7600  
Multifunction Controller or any controller capable of  
processing a 4 to 20 mA signal.  
Contents  
General ...............................................................................  
Features ..............................................................................  
Specifications ......................................................................  
Ordering Information ...........................................................  
Installation ...........................................................................  
Operation ............................................................................  
1
1
2
2
3
5
Copyright © 1996 Honeywell Inc.  
All Rights Reserved  
63-2150-5  
 
C7600A SOLID STATE HUNIDITY SENSOR  
20  
18  
16  
14  
12  
10  
· Attach the sensor to the wall with two 1/8 in. (3 mm)  
RH (%) I (mA)  
diameter screws.  
10  
20  
30  
40  
50  
60  
70  
80  
90  
18.4  
16.8  
15.2  
13.6  
12.0  
10.4  
8.8  
» Wire as shown in the Wiring section.  
Installing C7600 Solid State Humidity Sensor in  
Return Air Duct (See Fig. 3)  
7.2  
5.6  
8
NOTE: Installers need to supply the following: sheet metal  
cutter or snips; drill with 1/16 in. (2 mm), 1/8 in.  
(3 mm) and 1/2 in. (13 mm) bits; screwdrivers; 1/2 in.  
(13 mm) rubber grommet; eight self-tapping sheet  
metal screws; and two 1/8 in. (3 mm) by 3/4 in.  
(19 mm) machine screws with lockwashers and nuts.  
6
4
0
10 20 30 40 50 60 70 80 90 100  
HUMIDITY IN % RH  
M3130  
Fig. 2. C7600A output current vs. relative humidity.  
³ Cut a 5 in. (127 mm) by 6 in. (152 mm) rectangular  
hole in one side of the return air duct.  
INSTALLATION  
· Center the sensor on a 6 in. (152 mm) by 7 in. (178 mm)  
piece of sheet metal. Mark locations for mounting  
screws and for a hole for the control wire.  
When Installing this Product…  
1. Read these instructions carefully. Failure to follow them  
could damage the product or cause a hazardous  
condition.  
» Drill two 1/8 in. (3 mm) mounting holes for the sensor  
and one 1/2 in. (13 mm) hole for the control wire.  
2. Check the ratings given on the product to make sure  
the product is suitable for your application.  
3. Installer must be a trained, experienced service  
technician.  
¿ Drill eight starting holes in the sheet metal rectangle for  
self-tapping sheet metal screws.  
4. Checkout according to instructions provided with the  
controller before leaving installation.  
´ Center sheet metal rectangle over opening in duct so  
there is a 1 in. (25 mm) overlap on all four sides. Then  
mark the eight sheetmetal screw locations on the duct.  
CAUTION  
² Drill eight starting holes in the duct for self-tapping  
Disconnect power before installation to prevent  
electrical shock or equipment damage.  
sheet metal screws.  
Attach sensor to sheet metal rectangle with 1/8 in.  
(3 mm) by 3/4 in. (19 mm) machine screws, washers  
and nuts. Attach the machine screws from the outside  
of the sheet metal to eliminate protrusions and possible  
sharp edges.  
Location  
When selecting the location, make certain that the humidity  
sensor is not exposed to rain, snow, or direct sunlight. The  
C7600A Solid State Humidity Sensor is designed to operate  
in 500 ft/min minimum airflow.  
º Place a rubber grommet in the 1/2 in. (13 mm) hole in  
the sheet metal to protect the control wires from  
abrasions.  
Mounting  
The C7600A Solid State Humidity Sensor can be mounted in  
any position; however, the sensor must be installed where it  
is exposed to freely circulating air, with at least 500 ft/min  
airflow.  
¾ Put the control wires through the 1/2 in. (13 mm) hole  
and wire as shown in the Wiring section.  
µ Attach the sheet metal rectangle to the duct with self-  
tapping sheet metal screws. Make sure that airflow over  
the sensor is as shown in Fig. 3.  
Mounting the C7600 Solid State Humidity  
Sensor Outdoors  
³ Select a location protected from rain, snow or direct  
sunlight.  
3
63-2150—5  
 
C7600A SOLID STATE HUMIDITY SENSOR  
7
(127)  
5
AIR FLOW  
6
(152)  
AIR FLOW  
8
1
6
(152)  
AIR FLOW  
AIR FLOW  
3
7
(178)  
9
4
2
10  
5,6  
M5242A  
Fig. 3. Installing C7600A Solid State Humidity Sensor in return air duct.  
63-2150—5  
4
 
C7600A SOLID STATE HUNIDITY SENSOR  
Wiring  
OPERATION  
Disconnect the power supply before beginning wiring to  
prevent electrical shock or equipment damage. All wiring  
must comply with applicable codes and ordinances.  
Follow the wiring information furnished by the controller  
manufacturer or refer to Fig. 4 for a typical wiring hookup.  
Note and follow polarity markings for hookup.  
The C7600A Solid State Humidity Sensor provides a 4 to 20  
mA output signal that is inversely proportional to the relative  
humidity of the return air.  
The sensing element in the C7600A Solid State Humidity  
Sensor is a humidity-sensitive polyamide film that changes  
capacitance with a change in humidity. This change in  
capacitance is converted by a printed circuit board assembly  
to an output current between 4 and 20 mA. The output current  
is used by an analog or a microprocessor-based controller to  
measure and control humidity.  
W7600  
=8  
=7  
=6  
=5  
=4  
=3  
8=  
7=  
6=  
DIGITAL  
OUTPUTS  
5=  
DIGITAL  
INPUTS  
D COM=  
=2  
=1  
=D COM  
4=  
3=  
2=  
DIGITAL  
OUTPUTS  
1=  
D COM=  
=24 VDC(+)  
=8  
=7  
=6  
ANALOG  
INPUTS  
=5  
=A COM  
4=  
3=  
2=  
ANALOG  
OUTPUTS  
1=  
A COM=  
=20 VDC(+)  
=4  
=3  
=2  
=1  
=A COM  
+
ANALOG  
INPUTS  
4=  
3=  
2=  
S7600A  
1=  
C7600C  
RETURN AIR  
HUMIDITY SENSOR  
1
GND=  
V2=  
V1=  
24 VAC  
OUT  
1
237 OHM, 1 PERCENT, 1/8 WATT  
METAL FILM RESISTOR.  
24 VAC  
INPUT  
V2=  
V1=  
=V1  
=V2  
=GND  
24 VAC  
OUT  
M3128  
Fig. 4. Wiring C7600A Solid State Humidity Sensor to W7600.  
5
63-2150—5  
 
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
P.O. Box 524  
Minneapolis MN 55408-0524  
Home and Building Control  
Honeywell Asia Pacific Inc.  
Room 3213-3225  
Sun Hung Kai Centre  
No. 30 Harbour Road  
Wanchai  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
M2H 2C9  
Hong Kong  
Honeywell Latin American Division  
Miami Lakes Headquarters  
Honeywell Europe S.A.  
3 Avenue du Bourget  
14505 Commerce Way Suite 500  
Miami Lakes FL 33016  
B-1140 Brussels Belgium  
Helping You Control Your World®  
Printed in U.S.A. on recycled paper  
63-2150—5 G.H. Rev. 12-96  
containing at least 10%post-consumer paper fibers  
 

Graham Field SONAR 14423 2 User Manual
Graham Field SONAR GF TX5EMS User Manual
Hamilton Electronics Cassette Player HA 661 8 User Manual
Hamilton Electronics Cassette Player HA 802 User Manual
Harman Boiler SF160 User Manual
Harman Kardon Home Theater System HK6800 User Manual
Honeywell Boiler Series 4 User Manual
HP Hewlett Packard Personal Computer dv7 User Manual
Hunter Fan Outdoor Ceiling Fan M0021 01 User Manual
IBM Computer Monitor L180p User Manual